When apcupsd detects a UPS state change it calls apccontrol, which runs the executable in /etc/apcupsd that has the same name as the event and passes the UPS name as the first argument. apcupsd has no native webhook, so an event script pushes the events to Flashduty in the Standard Alert Event format: onbattery triggers an alert and offbattery recovers it.

In Flashduty On-call

Get an integration push URL in either of the two ways below. Choose the Standard Alert Event integration type in both, not apcupsd.

Use a dedicated integration

  1. In the Flashduty console, go to Channels and open a channel
  2. Go to Settings → Integrations → Dedicated integrations and click Add integration
  3. Select Standard Alert Event and click Save
  4. Open the generated integration card and copy the Push URL, in the form https://api.flashcat.cloud/event/push/alert/standard?integration_key=<integration key>

Use a shared integration

  1. In the Flashduty console, go to Integration Center → Alert Events
  2. Select Standard Alert Event and enter an integration name
  3. Configure the default route and select a channel. You can add more rules under Routing after creation
  4. Click Save and copy the generated Push URL

Configure in apcupsd

1

Create the push script on the apcupsd host

Where: The host running apcupsd › /etc/apcupsd/flashduty-notify.sh
2

Hook the script into the apcupsd events

Where: The host running apcupsd › /etc/apcupsd/ (executable files named after the events)apcupsd’s customization mechanism (see the apccontrol manual): create an executable file named after the event in /etc/apcupsd. apccontrol runs it first when the event occurs; if it exits with status 0, apccontrol continues with the event’s default action, and exit status 99 skips the default action. The script above always exits with 0, so it does not change apcupsd’s default behavior (including the shutdown sequence).The command below creates one event file per event that only calls the push script. Events that already have a file in the directory (the onbattery, offbattery, commfailure, commok and changeme sample scripts installed by apcupsd are such files) are not overwritten; the command tells you to add the call line near the top of the file yourself:
How events map to alerts:powerout (generated as soon as the UPS switches to battery) is not hooked: onbattery only fires when the outage lasts longer than ONBATTERYDELAY, which avoids alerts for momentary power dips.
3

Run the event scripts by hand on the apcupsd host and confirm

Where: Terminal on the host running apcupsdRun the event scripts by hand, first a trigger and then a recovery:
In Flashduty you should first see the alert UPS myups: on battery and then see it recover; the integration shows Latest event time, which means the setup works. Running onbattery by hand also runs whatever else the event file already contains; to test only the push, run /etc/apcupsd/flashduty-notify.sh onbattery myups directly.

Recovery and deduplication

  • onbattery, the failure events (failing, timeout, loadlimit, runlimit), offbattery and mainsback share the Alert Key apcupsd:<UPS name>:power: onbattery triggers the alert, a following failure event raises it to Critical, and it recovers when utility power returns
  • commfailure and commok, and battdetach and battattach, are paired
  • changeme and emergency have no matching recovery event. While a battery fault persists, apcupsd repeats changeme every 9 hours. After replacing the battery, close the alert manually in Flashduty, or enable the auto-resolve timeout on the channel, starting with 24 hours; if the battery has not been replaced, the next changeme triggers the alert again
  • Alerts of several UPS units do not affect each other: the Alert Key contains the UPS name (the name configured in apcupsd.conf)

Troubleshooting

  • No alert arrives: confirm the file named after the event exists in /etc/apcupsd and is executable, and that URL in flashduty-notify.sh is correct; run the event file by hand and check the output
  • The alert does not recover: confirm the recovery events (offbattery, mainsback, commok, battattach) are hooked too
  • Flashduty returns a parameter error: confirm URL is the full push URL, including integration_key
For more details, see the apcupsd apccontrol manual.